All products were acquired by from a sale of merchandise subject to a commercial insurance loss. is a secondary seller of products, is not affiliated with or sponsored by the manufacturer of the products and is not a manufacturer authorized seller of the products. Sale of this product by is not subject to the policies of the manufacturer. Any warranty offered by the manufacturer is not available to you as the purchaser. All products are NEVER USED but external packaging will have damage. Some items may be placed into other packaging to ensure safe shipping. All items are opened for inspection prior to shipment to ensure the best quality of products. guarantees your satisfaction. If you are not completely satisfied with a purchased product, within 30 days from the date of purchase, return the product in its packaging and will fully refund your money.

Description:

Insulated enclosure, flush mounting, rotary handle black grey, IP55_x

Insulated enclosure, E-PKZ0, H x W x D = 129 x 85 x 124 mm, flush-mounted, rotary handle, black/gray, IP55

Categories:
Low-voltage industrial components > Empty enclosure for switchgear

Motor-protective circuit-breakers PKZ (Accessories)

Product rangeAccessoriesSubrangeInstallation enclosuresAccessoriesInsulated enclosures for PKZ
with black-grey rotary knobDegree of ProtectionFront IP55For use withPKZM0-
+NHI or U or A
+NHI-E
+L-PKZ0 (2 off)NotesWith integrated PE(N) terminal.

Design verification as per IEC/EN 61439

Technical data for design verification
Rated operational current for specified heat dissipation0 AHeat dissipation per pole, current-dependent0 WEquipment heat dissipation, current-dependent0 WStatic heat dissipation, non-current-dependent0 WHeat dissipation capacity0 WOperating ambient temperature min.-25 COperating ambient temperature max.+40 CIEC/EN 61439 design verification
10.2 Strength of materials and parts10.2.2 Corrosion resistanceMeets the product standard’s requirements.10.2 Strength of materials and parts10.2.3.1 Verification of thermal stability of enclosuresMeets the product standard’s requirements.10.2 Strength of materials and parts10.2.3.2 Verification of resistance of insulating materials to normal heatMeets the product standard’s requirements.10.2 Strength of materials and parts10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effectsMeets the product standard’s requirements.10.2 Strength of materials and parts10.2.4 Resistance to ultra-violet (UV) radiationPlease enquire10.2 Strength of materials and parts10.2.5 LiftingDoes not apply, since the entire switchgear needs to be evaluated.10.2 Strength of materials and parts10.2.6 Mechanical impactDoes not apply, since the entire switchgear needs to be evaluated.10.2 Strength of materials and parts10.2.7 InscriptionsMeets the product standard’s requirements.10.3 Degree of protection of ASSEMBLIESDoes not apply, since the entire switchgear needs to be evaluated.10.4 Clearances and creepage distancesMeets the product standard’s requirements.10.5 Protection against electric shockDoes not apply, since the entire switchgear needs to be evaluated.10.6 Incorporation of switching devices and componentsDoes not apply, since the entire switchgear needs to be evaluated.10.7 Internal electrical circuits and connectionsIs the panel builder’s responsibility.10.8 Connections for external conductorsIs the panel builder’s responsibility.10.9 Insulation properties10.9.2 Power-frequency electric strengthIs the panel builder’s responsibility.10.9 Insulation properties10.9.3 Impulse withstand voltageIs the panel builder’s responsibility.10.9 Insulation properties10.9.4 Testing of enclosures made of insulating materialIs the panel builder’s responsibility.10.10 Temperature riseThe panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.10.11 Short-circuit ratingIs the panel builder’s responsibility. The specifications for the switchgear must be observed.10.12 Electromagnetic compatibilityIs the panel builder’s responsibility. The specifications for the switchgear must be observed.10.13 Mechanical functionThe device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

Technical data ETIM 7.0

Low-voltage industrial components (EG000017) / Empty enclosure for switchgear (EC000712)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Component for low-voltage switching technology / Empty housing for switch devices (ecl-ss10.0.1-27-37-13-01[AKN343014])
Material housingPlasticWidth85 mmHeight129 mmDepth80 mmWith transparent coverNoSuitable for emergency stopNoModelBuilt-inDegree of protection (IP)IP55Degree of protection (NEMA)Other

Approvals

Product StandardsUL 508; CSA-C22.2 No. 14; IEC60947-4-1; CE markingUL File No.E36332UL Category Control No.NLRVCSA File No.165628CSA Class No.3211-05North America CertificationUL listed, CSA certifiedSpecially designed for North AmericaNoDegree of ProtectionIEC: Front IP55, UL/CSA Type: 1, 12, 3R